Voltage Regulation:It is a measure of change in the voltage magnitude between sending end and receiving end of a component, such as Transmission or Distribution line.
Voltage regulation Formula:
Vs
Part of Distribution System | Urban Area (%) | Suburban Area (%) | Rural Area (%) |
Up to Transformer | 2.5 | 2,5 | 2.5 |
Up to Service Main | 3 | 2 | 0.0 |
Up to Service Drop | 0.5 | 0.5 | 0.5 |
Total | 6.0 | 5.0 | 3.0 |
Voltage variations in 33 kV and 11kV feeders should not exceed the following limits at the farthest end under peak load conditions and normal system operation regime.
- Above 33kV (-) 12.5% to (+) 10%.
- Up to 33kV (-) 9.0% to (+) 6.0%.
- Low voltage (-) 6.0% to (+) 6.0%
Sometimes it can be difficult to achieve the required voltage, especially in rural areas . Part of the reason for the high voltage drop in rural areas it due to the fact that these areas are usually further was from the electricity supplies. Therefore, the power lines have to be extended over long distances, resulting in higher line losses. Power theft is a further factor which can contribute to voltage drops in rural areas. In these cases, 11/0.433 kV may be used in place of normal 11/0.4 kV distribution transformers .
Method to calculate % Voltage Regulation:
Method -1(Distance base )
Method-2(Load base):
Voltge drop at Load A
- Load Current at Point A (I) = KW / 1.732xVoltxP.F
- Load Current at Point A (I) =1500 / 1.732x11000x0.8 = 98 Amp.
- Required No of conductor / Phase =98 / 205 =0.47 Amp =1 No
- Voltage Drop at Point A = ( (√3x(RCosΦ+XSinΦ)xI ) / (No of Conductor/Phase x1000))x Length of Line
- Voltage Drop at Point A =((1.732x (0.272×0.8+0x0.6)x98) / 1×1000)x1500) = 57 Volt
- Receiving end Voltage at Point A = Sending end Volt-Voltage Drop= (1100-57) = 10943 Volt.
- % Voltage Regulation at Point A = ((Sending end Volt-Receiving end Volt) / Sending end Volt) x100
- % Voltage Regulation at Point A = ((11000-10943) / 11000)x100 = 0.51%
- % Voltage Regulation at Point A =0.51 %
Voltage drop at Load B
- Load Current at Point B (I) = KW / 1.732xVoltxP.F
- Load Current at Point B (I) =1800 / 1.732x11000x0.8 = 118 Amp.
- Distance from source= 1500+1800=3300 Meter.
- Voltage Drop at Point B = ( (√3x(RCosΦ+XSinΦ)xI ) / (No of Conductor/Phase x1000))x Length of Line
- Voltage Drop at Point B =((1.732x (0.272×0.8+0x0.6)x98) / 1×1000)x3300) = 266 Volt
- Receiving end Voltage at Point B = Sending end Volt-Voltage Drop= (1100-266) = 10734 Volt.
- % Voltage Regulation at Point B= ((Sending end Volt-Receiving end Volt) / Sending end Volt) x100
- % Voltage Regulation at Point B= ((11000-10734) / 11000)x100 = 2.41%
- % Voltage Regulation at Point B =2.41 %
Voltage drop at Load C
- Load Current at Point C (I) = KW / 1.732xVoltxP.F
- Load Current at Point C (I) =2000 / 1.732x11000x0.8 = 131 Amp
- Distance from source= 1500+1800+2000=5300 Meter.
- Voltage Drop at Point C = ( (√3x(RCosΦ+XSinΦ)xI ) / (No of Conductor/Phase x1000))x Length of Line
- Voltage Drop at Point C =((1.732x (0.272×0.8+0x0.6)x98) / 1×1000)x5300) = 269 Volt
- Receiving end Voltage at Point C = Sending end Volt-Voltage Drop= (1100-269) = 10731 Volt.
- % Voltage Regulation at Point C= ((Sending end Volt-Receiving end Volt) / Sending end Volt) x100
- % Voltage Regulation at Point C= ((11000-10731) / 11000)x100 = 2.44%
- % Voltage Regulation at Point C =2.44 %
Here Trail end Point % Voltage Regulation is 2.41% which is in permissible limit.
Method-2
- Load Current at Point A (I) = KW / 1.732xVoltxP.F
- Load Current at Point A (I) =1500 / 1.732x11000x0.8 = 98 Amp.
- Distance from source= 1.500 Km.
- Required No of conductor / Phase =98 / 205 =0.47 Amp =1 No
- Voltage Drop at Point A = (I x (RcosǾ+XsinǾ)x Length ) / V (Phase-Neutral))x100
- Voltage Drop at Point A =((98x(0.272×0.8+0x0.6)x1.5) / 1×6351) = 0.52%
- % Voltage Regulation at Point A =0.52 %
Voltage drop at Load B
- Load Current at Point B (I) = KW / 1.732xVoltxP.F
- Load Current at Point B (I) =1800 / 1.732x11000x0.8 = 118 Amp.
- Distance from source= 1500+1800=3.3Km.
- Required No of conductor / Phase =118 / 205 =0.57 Amp =1 No
- Voltage Drop at Point B = (I x (RcosǾ+XsinǾ)x Length ) / V (Phase-Neutral))x100
- Voltage Drop at Point B =((118x(0.272×0.8+0x0.6)x3.3)/1×6351) = 1.36%
- % Voltage Regulation at Point A =1.36 %
Voltage drop at Load C
- Load Current at Point C (I) = KW / 1.732xVoltxP.F
- Load Current at Point C (I) =2000 / 1.732x11000x0.8 = 131Amp.
- Distance from source= 1500+1800+2000=5.3Km.
- Required No of conductor / Phase =131/205 =0.64 Amp =1 No
- Voltage Drop at Point C = (I x (RcosǾ+XsinǾ)x Length ) / V (Phase-Neutral))x100
- Voltage Drop at Point C =((131x(0.272×0.8+0x0.6)x5.3)/1×6351) = 2.44%
- % Voltage Regulation at Point A =2.44 %
Here Trail end Point % Voltage Regulation is 2.44% which is in permissible limit.
Simple and practical method to measure Voltage Regulation in a distribution system:
1St measure staring end voltage of a DTR as Vs and then trail end voltage of a DTR as Vr then Voltage Regulation easily calculated.
For Vs=(Vry+Vyb+Vrb)/3
Vr=(Vry+Vyb+Vrb)/3
Vry:-Phase voltage between r and y phase
How to improve Voltage Regulation in a distribution line:
Comments
Post a Comment
If any doubts let me know..