XLPE cable current carrying capacity table | Different current carrying capacity in air and ground

 Hello friends,Today I will share some technical knowledge about Current carrying capacity of 3Phase  XLPE UG Cable.

3core XLPE


4 core XLPE
Let's start :Before discussion, full form of XLPE is Cross linked Poly Ethylene.It can withstand in high temperature and cross-linked features more moisture resistance.


By considering Size ,there are various sizes of 3 core cable available.Let us discuss their sizes with current carrying capacity.Their current carrying capacities are different according to installation i.e in laying ground and in air.

Size:

1)50 mm2 130amp(Ground),140amp(Air)
 2)95mm2(185Amp in Ground,200Amp in Air) 
3)150mm2(235Amp in ground,265Amp in Air)
4)185mm2(270Amp in Ground,310Amp in Air)
5)240 mm2(305Amp in Ground,345Amp in Air)
6)300 mm2(340Amp in Ground,396Amp in Air)

In above, every one may have some question that how current carrying capacity of a cable increased in air?I can answer this way that wind speed is major factor that affect current carrying capacity in air.When wind speed rises current carrying capacity of a cable increases.
 And in ground, thermal resistance does  major impact on cable . Thermal Resistances increases with the increase burial depth and current carrying capacity deceases.

Conclusion: I always share my knowledge through my  blog. Please comments if you like or any improvement.

Also read:






Comments

  1. 3Cx185mm2 XLPE UG Cable has current carrying is 270 amp in Ground and 310Amp in Air.

    ReplyDelete

Post a Comment

If any doubts let me know..

Popular posts from this blog

11KV ABC cable current carrying capacity

Let us discuss about Size and current carrying capacity of a  11 KV 3x120 mm2 AB Cable. Before getting answer we have to know about Technical Specification.The Technical Specification as below. TECHNICAL SPECIFICATION FOR 11KV AB Cable( AERIAL BUNCHED CABLES)  and XLPE insulated (CROSSED LINKED POLYETHYLENE DRY GAS CURED/WET CURED) FOR OVERHEAD LINES. 1. SCOPE  This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched Cables for overhead lines. 2. COMPOSITION OF THE CABLE The composite cable shall comprise three single-core cables twisted around a bare aluminium alloy messenger wire, which will carry the weight of the cable. 3. RATED VOLTAGE The rated voltage of the cables shall be 6.35KV/11KV and the maximum operating voltage shall be 12 KV. 4. APPLICABLE STANDARDS Unless otherwise stipulated in this Specification, the following Standards shall be applicable: i) IS: 7098 (Part-II) - 1985 – Cross linked Polyethylene Insulated PVC Sheathed Cables ii) IS: 8130-1984 -

Minimum Electrical Clearance

Minimum Electrical Clearance As Per BS:162. INDOOR Voltage in KV Phase to earth in mm Phase to phase in mm 0.415 15.8 19.05 0.600 19.05 19.05 3.3 50.8 50.8 6.6 63.5 88.9 11 76.2 127.0 15 101.6 165.1 22 139.7 241.3 33 222.25 355.6 Minimum Electrical Clearance As Per BS:162. OUTDOOR Voltage in KV Phase to earth in mm Phase to phase in mm 6.6 139.7 177.8 11 177.8 228.6 22 279.4 330.2 33 381 431.8 66 685.8 787.4 110 863.6 990.6 132 1066.8 1219.2 220 1778 2057.4   Minimum Working Clearance: OUTDOOR SWITCHYARD Voltage in KV To ground in mm Between section(mm) 11 2750 2500 33 3700 2800 66 4000 3000 132 4600 3500 220 5500 4500   Minimum Ground Clearance As Per IE-1956(Rule 77) Voltage in KV To ground in mtr 132 6.10 220 7.00 400 8.84 800 12.40     Minimum Clearance between Lines Crossing Each Other (IE-1957) System Voltage 132KV 220KV 400KV 800KV Low & Medium 3.05 4.58 5.49 7.94 11-66KV 3.05 4.58 5.49 7.94 132KV 3.05 4.58 5.49 7.94 220KV 4.58 4.58 5.49 7.94 400KV 5.49 5.49 5.49 7.94 800KV

How to calculate Voltage Regulation of 11 KV line

  Voltage Regulation: It is a measure of change in the voltage magnitude between sending end and receiving end of a component, such as Transmission or Distribution line. Voltage regulation Formula: %VR= Vs-Vr    x  100                 Vs Permissible Voltage Regulation in distrDistrib System: Permissible Voltage Regulation as per REC: Part of Distribution System Urban Area (%) Suburban Area (%) Rural Area (%) Up to Transformer 2.5 2,5 2.5 Up to Service Main 3 2 0.0 Up to Service Drop 0.5 0.5 0.5 Total 6.0 5.0 3.0 Voltage variations in 33 kV and 11kV feeders should not exceed the following limits at the farthest end under peak load conditions and normal system operation regime. Above 33kV (-) 12.5% to (+) 10%. Up to 33kV (-) 9.0% to (+) 6.0%. Low voltage (-) 6.0% to (+) 6.0% Sometimes it can be difficult to achieve the required voltage, especially in rural areas . Part of the reason for the high voltage drop in rural areas it due to the fact that these areas are usually further was from